Home   ::  Features & Specifications  ::  Comparision of Electromat & Rubber Mat  ::   Our Recent Exhibitions    ::   Contact Us

Who Should Use Products  
Where The Mats Should Be Used
Dielectric Measurement Method of Testing
Safety Instructions
Recent Projects
FEATURES AND SPECIFICATIONS
 
1.    SPECIFICATIONS
 
 A]  Physical Properties :-
1. Color  : Blue without Metallic Derivatives
2. Thickness :
  Voltage Systems Thickness
(A) Up to 3.3 KV -    2.0 mm thick
(B) Above 3.3 to 11 kV -   2.5 mm thick 
(C) 11 kV to 65 kV -    3.0 mm thick
 
  B] Test Parameters :-
 
S.NO. Details of the Test Unit Electromat, 2.0 mm thickness
1   Tensile Strength N/mm2   22.40
2   Elongation %   318.50
3   Insulation Resistance Mega Ohm   14, 94, 000
4   Die Electric withstand Test KV   30 KV for 1 min
5   Die Electric withstand Test KV   62.0
6   Effect of fire Second   1.0
7   Effect  of Acid, Alkali, Diesel
  & Transformer Oil
%   -19.8 & + 2.31 of Original value
8   Ageing Test %   -1.89  & + 4.10 of original value
9   Leakage Current Test in oil Ma   0.2 ma at 22 KV
 
II TYPICAL FEATURES:-
  1. All Products Tested By CPRI (The Leading Research and Test House for Power in India).
  2. High Dielectric Strength Up to 65 KV.
  3. Insulation Resistance Up to 1494000 Mega Ohm.
  4. Fire Retardant.
  5. Good Mechanical Properties To With Stand Load and Movement of Breaker Trolleys and Associated Electrical Equipment including heavy foot traffic.
  6. No Adverse Effect of Acids, Alkalis and Transformer Oil.
  7. Manufactured Without Any Metallic Derivatives
  8. Suitable For Both A.C & D.C Electrical Installations
  9. Easy To Install, Can Be Pasted.
  10. Water And Moisture Proof, Does Not Decay.
  11. High Tensile Strength and Elongation Properties
 
 
  
    Home   ::  Features & Specifications  ::  Comparision of Electromat & Rubber Mat  ::     Contact Us
 
Site Design & Promoted by : RK Sharma