| IEC-61111 Standard |
IS: 15652:2006 Standard |
| Class |
Thickness
(MM) |
System
Voltage |
A.C
proof Voltage |
Break-Down Withstand voltage |
| 0 |
6.0 |
1KV |
5 KV |
10 KV |
| 1 |
6.0 |
7.5 KV |
10 KV |
20 KV |
| 2 |
8.0 |
17 KV |
15 KV |
30 KV |
| 3 |
11.0 |
26.5 KV |
20 KV |
40 KV |
| 4 |
14.0 |
36 KV |
25 KV |
50 KV |
|
| Class |
Thickness
(MM) |
System
Voltage |
A.C
proof Voltage |
Break-Down Withstand voltage |
| A |
2.0 MM |
upto 3.3 KV |
10 KV |
30 KV |
| B |
2.5 MM |
upto11 KV |
22 KV |
45 KV |
| C |
3.0 MM |
upto 33 KV |
36 KV |
65 KV |
| D |
3.5 MM |
upto 66 KV |
70 KV |
110 KV |
| -- |
-- |
-- |
-- |
-- |
|
|
| |
| Fire Retardant Properties |
| IEC-61111 Standard |
IS: 15652:2006 Standard |
| i.)The propagation of the flame on the test piece shall be observed for 55 second after the withdrawal of the testing flame. |
i.) Fire should extinguish within 5 second after removal of blue flame. |
|
| |
| As you will observe from above that the fire retardant properties as per IS: 15652:2006 is much better which is prime concern for safety for Oil-Rig area , thickness of the mat is much less & it is pastable type & have good Mechanical properties to withstand load & smooth breaker trolleys movement. |
| |
| |